Lightning protection system installation work, Electrolux factory construction project, Rayong Province

Sukhumvit 26 Hotel7 result

 

Bongkot 2

Lightning rod, LIVA brand, model LAP-DX-250, installed on the roof, 6 meter high pole, pulling 1 layer of rope.

Bare copper grounding cable, size 95 sq.mm., threaded in 1” UPVC pipe with grounding system.

 

Bongkot 3  

 Assembling the lightning rod head

  Use a fishtail with a cable cover. Connect to the connector before threading the galvanized pipe.

Sukhumvit 26 Hotel2 result   Bongkot 4

Four-sided clamping sling Keep it waterproof. Work under the roof is fixed to the frame under the roof for strength and good wind resistance. Use a stainless steel cone to cover the base of the pole with waterproofing. No more worries about water leaks.

PMM จ.ระยอง08

Cable number 95 Sq.mm threaded in UPVC pipe 1"

 

Sukhumvit 26 Hotel3 result  

Lightning counter and test block

Lightning counter, brand LIVA, model LSC-LX01/A COUNTER STRIKE RECORD

 

Sukhumvit 26 Hotel5 result  PMM จ.ระยอง06

Ground system

The area is mountainous and mostly rocky. and the soil is filled in, causing the ground value to be higher than the standard. But with more than 18 years of experience

The team was able to achieve a ground value that was within standard criteria. The value was 2.10 ohms (Ohm), which was satisfactory.

The equipment uses a 5/8" copper-plated ground rod connected to a wire number 95 Sq.mm because there is little ground space. Use the method of making a spreading ground (Star)

 

The resistance value of the grounding system must comply with the EST regulations and not exceed 5 ohms for the efficiency of the system.
 
A good lightning rod should be tested. and inspect the system annually

 

Recommendations for lightning protection system work

 The resistance of the grounding system should be checked every year to ensure that the resistance is within the standard, not exceeding 5 ohms.

     and not more than 20 % of the first test measurement of the grounding system installation in the following year.

Check the wiring system and equipment completely to ensure that the system works efficiently. annually

 

Ask for a special price. เครื่องนับฟ้าผ่า Lightning strike counter LSC-LX01-05

LSC-LX01-05 Lightning strike counter 

Standard lightning strike counter 

เครื่องนับจำนวนฟ้าผ่าเพื่อเป็นการเก็บข้อมูลในแต่ละช่วงของปีในการนำข้อมูลมาพิจารณาตรวจสอบหัวล้อฟ้า และระบบกราวด์ให้อยู่สถาพที่พร้อมในการทำงาน

ตัวเครื่อง กันน้ำ กันฝุ่น IP67
หน่วยนับ 6 หลัก รีเซ็ตไม่ได้
ทนกระแสฟ้าผ่าสูงสุด  150kA
ตรวจจับกระแสผ่าฟ้าตั้งแต่  1kA ที่ 8/20 MicroSec.
ทำงานในช่วงอุณหภูมิ  -30 ถึง 80 องศาฟาเรนไฮต์

 

 

ระบบป้องกันฟ้าผ่า, Early streamer emission (ESE) , หัวล่อฟ้า, Grounding system, Lightning Protection System (LPS), สายล่อฟ้า, Acon Plus Co., Ltd.